SAT-LCL 36KW Rack wokwera AC/DC madzi ozizira katundu
- Description:
-
1). Load simulation
2). Control mode
3). Temperature protection
4). Monitoring function
5). Parallel expansion - Lumikizanani Tsopano
Tel: + 86 88115682
E-mail: sales@aitelong.com
- Kufotokozera
-
With the water cooling of data centers, "liquid cooling" technology is the most reliable and feasible solution to reduce the energy consumption of data centers. Liquid cooling load can simulate the actual heat generation and power consumption of real servers in the server room, detect the liquid cooling effect of the server room and the power safety of the server room lines, and provide data basis and testing methods for the reliability of the server room system. The liquid cooling load box adopts a modular design, which is easy to maintain and replace. It can be used alone or in parallel with multiple machines, and each gear can be adjusted.
l Load simulation: can simulate the actual heating situation of the server in the computer room, cooling effect, power supply load capacity, line reliability verification, etc.;
l Control mode: can control the load power increase/decrease through a multi-position switch;
l Temperature protection: when the load temperature exceeds the set safety threshold, an audible and visual alarm prompts;
l Monitoring function: the device can be equipped with an LCD display to display the temperature, flow rate, alarm and other information of the inlet and outlet water;
l Parallel expansion: can realize parallel testing of multiple loads to meet the needs of high-power testing.
Zolemba zamakono
Voliyumu/mafupipafupi ovotera
AC three-phase, single-phase voltage:220V/50Hz
DC 270V
adavotera mphamvu
36KW (single-phase 12kW@ AC220V/50Hz)
Load step:Zamgululi,Zamgululi,Zamgululi,Zamgululi,3kW;(A,B,C three steps)
When the voltage changes, the gear power changes based on AC220V according to Ohm's law.
Load materials
PTC
Mphamvu yamagetsi
1
Heat transfer efficiency
≥95%
Fully load accuracy
Accuracy≤±5%
Main circuit power interface
2 per phase, interface with protective cover
Katundu Njira
Gear switch(miniature circuit breaker),manual loading
Mphamvu yolamulira
Adopt the power interface under test for power supply
Mulingo wodzipatula
AC1000V,isolation resistance ≥10MΩ
Inlet water temperature
2-100 °
Water interface
1 inlet pipe and 1 return pipe, clamp-type quick connector,
pipe diameter: DN25
Anzanu
Liquid cooling container or resistor withstands 1.0MPa working pressure, and the ultimate test pressure is 1.5 times the working pressure
Kuwotcha mpweya
No leakage for 2 hours under 1Mpa pressure
Madzi oyenda
1-10m3/h
Njira yozizira
High grade pure water cooling
Isolation grade
F
Gawo lazachitetezo
IP24
Njira yogwirira ntchito
Kugwira ntchito mosalekeza
Chitoliro chakuthupi
Stainless steel 304
Pannel display
The load panel has a power working indicator light and a fault alarm indicator light.
It has an inlet and outlet water temperature sensor to display the temperature and current, voltage, and power data (LED instrument), and the sensor accuracy is 0.5 level.
Kuteteza kutentha kwambiri
The load carries the water temperature monitoring of the inlet and outlet. When the water temperature is abnormal, the alarm prompts and the load is unloaded. The upper limit of the inlet and outlet temperature alarm is adjustable (default: 80℃)
Chitetezo chopitilira
When the switch is in overcurrent protection, the switch trips and cuts off the overcurrent load;
Chitetezo cha pansi
The ground wire of the load input port is connected to the chassis, and the chassis grounding terminal is for users to use for grounding.
Short chitetezo dera
The load short-circuit switch trips and cuts off the load
Load modular design
The load adopts modular design and can be used as a single module or in parallel
kukula
430mm*720mm*289mm(L*W*H) blue
Kunenepa
55kg
thiransipoti
The side is equipped with lifting handles for easy transportation;
ntchito kutentha
-15℃ ~+ 70℃
Mvula yamtendere
0-95% RH,Zosaloleza
Kutalika
≤2500m
Kupanikizika kwa ma atmospheric
86~106kPa
Maimidwe akukhazikitsa
For indoor use, no flammable gas around